- No flame propagation; thermally stable for more than 60 minutes at 200 °C
- Hydrochloric acid content less than 19%; oxygen index more than 29%
- Smoke density rating less than 60%
- 20 to 63 mm, in LMS, MMS and HMS
Sizes
From the AKG product leaflet and IS 9537 dimensions.
Tap a size to add it to your quote list.
FRLS conduit sizes
| Item | Size, mm | Mechanical strength | Max. OD, mm | Min. OD, mm | Min. ID, mm |
|---|---|---|---|---|---|
| 20 | Light | 20 | 19.70 | 17.40 | |
| 20 | Medium | 20 | 19.70 | 16.90 | |
| 20 | Heavy | 20 | 19.70 | 15.80 | |
| 25 | Light | 25 | 24.60 | 22.10 | |
| 25 | Medium | 25 | 24.60 | 21.40 | |
| 25 | Heavy | 25 | 24.60 | 20.60 | |
| 32 | Light | 32 | 31.60 | 28.60 | |
| 32 | Medium | 32 | 31.60 | 27.80 | |
| 32 | Heavy | 32 | 31.60 | 26.60 | |
| 40 | Light | 40 | 39.60 | 35.80 | |
| 40 | Medium | 40 | 39.60 | 35.40 | |
| 40 | Heavy | 40 | 39.60 | 34.40 | |
| 50 | Light | 50 | 49.50 | 45.10 | |
| 50 | Medium | 50 | 49.50 | 44.30 | |
| 50 | Heavy | 50 | 49.50 | 43.20 | |
| 63 | Light | 63 | 62.40 | 57.00 |
AKG at Dynamic Solutions, Jammu
FRLS conduit is the right choice for hospitals, hotels, schools, malls, data centres and high-rise buildings where low smoke and low halogen materials are specified. Dynamic Solutions supplies AKG FRLS conduits in Jammu and across J&K, matched with Polycab FR-LSH house wires for a complete fire-safe wiring system.