Home / Wires & cables / Copper armoured cables / 1 core 10 sq mm copper armoured cable (2XWaY)
Polycab · Copper armoured cables
Polycab 1 core 10 sq mm copper armoured cable (2XWaY)
Today's rate on request

Specifications
- Brand
- Polycab
- Polycab type
- 2XWaY
- Cores × size
- 1 × 10 sq mm
- Conductor
- Stranded copper, class 2 to IS 8130
- Insulation
- XLPE
- Armour
- Aluminium wire armour, non-magnetic, for single core on AC
- Outer sheath
- PVC, type ST2
- Overall diameter
- About 12 mm
- Weight
- About 219 kg/km
- Bending radius
- 12 × overall diameter (about 144 mm, fixed installation)
- Voltage
- 650/1100 V
- Temperature
- Maximum conductor temperature 90°C
- Standards
- IS 7098 (Part 1)
Construction

- Stranded copper conductor
- XLPE insulation
- Aluminium armour (the picture shows the flat strip version)
- Extruded PVC type ST2 outer sheath
From the Polycab datasheet for this cable family.
Also known as
- 1C x 10 sq mm 2XWaY cable
- 1 core 10 sqmm copper armoured cable
- 10 sq mm 1 core Cu Ar XLPE cable
- Polycab 10 sq mm 1 core cable
Current rating
- Buried direct in ground
- 77 A
- In single way duct
- 70 A
- In air
- 71 A
Polycab figures at 40°C air, 30°C ground and 90°C conductor temperature. Derate for higher temperatures, grouped cables and long runs.
Other sizes in this cable
| Size | Dia. mm | Weight kg/km | In air |
|---|---|---|---|
| 10 sq mm | 12 | 219 | 71 A |
| 16 sq mm | 13 | 281 | 94 A |
| 25 sq mm | 14 | 390 | 126 A |
| 35 sq mm | 16 | 485 | 154 A |
| 50 sq mm | 17 | 608 | 187 A |
| 70 sq mm | 19 | 817 | 238 A |
| 95 sq mm | 22 | 1102 | 303 A |
| 120 sq mm | 23.5 | 1339 | 354 A |
| 150 sq mm | 24.5 | 1615 | 403 A |
| 185 sq mm | 26.5 | 1976 | 468 A |
| 240 sq mm | 29 | 2508 | 553 A |
| 300 sq mm | 31.5 | 3078 | 634 A |
| 400 sq mm | 36 | 3962 | 737 A |
| 500 sq mm | 39.5 | 4969 | 844 A |
| 630 sq mm | 43 | 6318 | 961 A |
| 800 sq mm | 48.5 | 7990 | 1077 A |
| 1000 sq mm | 54 | 10051 | 1188 A |
Uses
- Underground and buried feeders
- Main and sub-main distribution in plants and buildings
- Transformer to panel connections
- Outdoor runs on trays and in trenches
How to order
- Add it to your quote list or message us on WhatsApp with the length you need.
- We confirm today's price, availability and cut length.
- We deliver to your site or you collect from Bari Brahmna.
Email us
Send your sizes and lengths to Sales@dynamicsolutions9.com and we reply with a quotation.
Questions
What is the price of this cable?
Cable rates change with copper prices, so we quote today's rate per metre, coil or drum when you ask.
What is its current rating?
71 A in air and 77 A buried direct, and 70 A in a single way duct, as per the Polycab catalogue.
What are its diameter and weight?
About 12 mm overall diameter and about 219 kg per km, as per the Polycab datasheet.
How do I order?
Add it to your quote list or WhatsApp us the length. We confirm price and availability, then deliver across Jammu and Kashmir, Ladakh and Punjab, and pan-India for bulk orders.