Home / Wires & cables / Copper unarmoured cables / 2 core 16 sq mm copper unarmoured cable (2XY)
Polycab · Copper unarmoured cables
Polycab 2 core 16 sq mm copper unarmoured cable (2XY)
Today's rate on request

Specifications
- Brand
- Polycab
- Polycab type
- 2XY
- Cores × size
- 2 × 16 sq mm
- Conductor
- Stranded copper, class 2 to IS 8130
- Insulation
- XLPE
- Inner sheath
- PVC
- Armour
- None (unarmoured)
- Outer sheath
- PVC, type ST2
- Overall diameter
- About 14 mm
- Weight
- About 422 kg/km
- Bending radius
- 12 × overall diameter (about 168 mm, fixed installation)
- Voltage
- 650/1100 V
- Temperature
- Maximum conductor temperature 90°C
- Core colours
- Red, black
- Standards
- IS 7098 (Part 1)
Construction

- Stranded copper conductor
- XLPE insulation
- PVC type ST2 inner sheath
- Extruded PVC type ST2 outer sheath
From the Polycab datasheet for this cable family.
Also known as
- 2C x 16 sq mm 2XY cable
- 2 core 16 sqmm copper unarmoured cable
- 16 sq mm 2 core Cu UnAr XLPE cable
- Polycab 16 sq mm 2 core cable
Current rating
- Buried direct in ground
- 115 A
- In single way duct
- 96 A
- In air
- 108 A
Polycab figures at 40°C air, 30°C ground and 90°C conductor temperature. Derate for higher temperatures, grouped cables and long runs.
Other sizes in this cable
| Size | Dia. mm | Weight kg/km | In air |
|---|---|---|---|
| 1.5 sq mm | 10 | 140 | 27 A |
| 2.5 sq mm | 10.9 | 173 | 36 A |
| 4 sq mm | 12.5 | 165 | 48 A |
| 6 sq mm | 13.5 | 210 | 61 A |
| 10 sq mm | 16 | 300 | 83 A |
| 16 sq mm | 14 | 422 | 108 A |
| 25 sq mm | 17 | 636 | 140 A |
| 35 sq mm | 19 | 817 | 172 A |
| 50 sq mm | 21 | 1054 | 208 A |
| 70 sq mm | 23 | 1453 | 262 A |
| 95 sq mm | 26.5 | 1966 | 322 A |
| 120 sq mm | 28.5 | 2413 | 368 A |
| 150 sq mm | 32 | 2935 | 419 A |
| 185 sq mm | 35.5 | 3676 | 482 A |
| 240 sq mm | 39.5 | 4750 | 566 A |
| 300 sq mm | 43.5 | 5918 | 644 A |
| 400 sq mm | 49 | 7495 | 734 A |
16 sq mm in other cores
Uses
- Feeders on covered trays and in ducts
- Indoor distribution in plants and buildings
- Panel to panel connections
How to order
- Add it to your quote list or message us on WhatsApp with the length you need.
- We confirm today's price, availability and cut length.
- We deliver to your site or you collect from Bari Brahmna.
Email us
Send your sizes and lengths to Sales@dynamicsolutions9.com and we reply with a quotation.
Questions
What is the price of this cable?
Cable rates change with copper prices, so we quote today's rate per metre, coil or drum when you ask.
What is its current rating?
108 A in air and 115 A buried direct, and 96 A in a single way duct, as per the Polycab catalogue.
What are its diameter and weight?
About 14 mm overall diameter and about 422 kg per km, as per the Polycab datasheet.
How do I order?
Add it to your quote list or WhatsApp us the length. We confirm price and availability, then deliver across Jammu and Kashmir, Ladakh and Punjab, and pan-India for bulk orders.